CFM per ton: the chart, and the duct size that carries it
The rule is 400 CFM per ton of cooling, so a 3 ton system moves 1,200 CFM. The Reference tab has the table, and putting 1,200 into the ductulator gives a 14.6 in exact duct, a 16 in round.
What does the 400 CFM per ton table say?
Find it under Reference > Airflow per ton of cooling. DuctCalc lists seven common sizes with the kW equivalent and the metric airflow.
| Tons | kW | CFM | L/s |
|---|---|---|---|
| 1.5 | 5.3 | 600 | 283 |
| 2 | 7.0 | 800 | 378 |
| 2.5 | 8.8 | 1,000 | 472 |
| 3 | 10.6 | 1,200 | 566 |
| 3.5 | 12.3 | 1,400 | 661 |
| 4 | 14.1 | 1,600 | 755 |
| 5 | 17.6 | 2,000 | 944 |
The footer adds the exceptions: dry climates run up to 450 CFM per ton, and humid climates or heat pumps in heating often drop to 350. The table is fixed at 400, so for 450 or 350 you multiply yourself and type the CFM.
BTU to CFM calculator: HVAC airflow, tons and kW
- Distance between bends
- Shrink
- Multiplier
Enter numbers of zero or more; the set or the roll must be above zero.
Showing the worked example. Turn on JavaScript to calculate your own numbers.
Sensible heat in standard air: BTU/h = 1.08 × CFM × ΔT (°F). 1 ton = 12,000 BTU/h and 1 kW = 3,412.14 BTU/h. 400 CFM per ton is a rule of thumb (350 to 450 depending on climate and coil). A quick check, not a Manual J load calculation or a duct design.
From tons to a duct size
- Look up the airflow: 3 tons is 1,200 CFM.
- Go to the Ductulator tab, Size a duct, and type 1200 in Airflow.
- With Friction rate at 0.1, Required round duct reads 14.6 in at 1,028 fpm.
- The stock line says 16 in at 859 fpm and 0.064 in.wg/100ft.
Look at the badge here. The exact 14.6 in would be above the 1,000 fpm maximum for a residential supply main, but the app rates the stock size, and 16 in at 859 fpm is Within recommended range. A 14 in duct is the one that bites: 1,123 fpm and 0.124. An 18 in is quiet at 679 fpm and 0.036, and costs more metal.
If the trunk will be rectangular, the Rectangular equivalents card starts with 14 x 14 and 16 x 12, and goes on through 20 x 10 and 26 x 8 to 36 x 6 for the same 1,200 CFM. The last one gets the 6:1 chip.
What this is not
It is a trunk size for the equipment airflow. Splitting the air to rooms needs the room loads, and each branch is then a separate calculation with its own CFM. Run Size a duct once per branch and Name this duct run in History to keep them straight.