Recommended duct velocity: the chart, and checking a real duct
For residential supply mains the app uses 700 to 900 fpm with a 1,000 fpm ceiling; branches and returns sit lower. Type the airflow and the duct you have and a coloured badge says whether the speed is in range.
What velocities does DuctCalc use?
There are six applications. Each has a recommended band, which you design inside for quiet, and a maximum, which you do not exceed on purpose.
| Application | Recommended | Maximum |
|---|---|---|
| Residential · supply-air main | 700-900 | 1,000 |
| Residential · supply-air branch | 500-700 | 900 |
| Residential · return air | 500-700 | 800 |
| Commercial · supply-air main | 1,200-1,500 | 2,000 |
| Commercial · supply-air branch | 800-1,000 | 1,300 |
| Commercial · return air | 800-1,000 | 1,500 |
The same table sits offline under Reference > Recommended air velocities, in m/s if the app is set to metric. The footer there tells you to treat the maximum as a hard ceiling.
Duct size and air velocity from airflow
- Distance between bends
- Shrink
- Multiplier
Enter numbers of zero or more; the set or the roll must be above zero.
Showing the worked example. Turn on JavaScript to calculate your own numbers.
Round diameter D = √(4Q ÷ (π·V)), velocity v = Q ÷ area. The rectangular side uses the Huebscher equivalent De = 1.30·(a·b)^0.625 ÷ (a+b)^0.25 (ASHRAE Fundamentals). Standard sizes vary by market and the velocity is the real one in the duct you pick. It does not size friction loss, noise or fittings: follow your code and the design.
How do you check a duct you already have?
- Open Check a duct and tap Round duct (or Rectangular duct).
- Enter the Airflow and the Diameter, or the Width and Height.
- Read Air velocity and the badge underneath.
- Tap the line under the badge to change the Application. It is the same choice as Settings > Check velocity against.
One duct, four verdicts
Take a 6 in galvanized round and judge it as a Residential · supply-air branch (500 to 700 fpm, maximum 900):
| Airflow | Velocity | Badge |
|---|---|---|
| 100 CFM | 509 fpm | Within recommended range |
| 150 CFM | 764 fpm | Above recommended band · check noise |
| 200 CFM | 1,019 fpm | Over maximum · resize |
The fourth state is Below range · quiet, duct oversized, which you get with the same branch band if you run 400 CFM through a 14 in duct (374 fpm). It is shown in grey, not amber: a big duct is not a fault, it is just more sheet metal than you needed.
What the badge does not tell you
It compares velocity with a table. It does not measure noise, and there is no application for a bedroom or a studio. A grille, a damper or an elbow right after the duct makes more noise than the straight run, and none of that is in the calculation.